電能計量裝置存在的誤差為電能計量綜合誤差,是由電能表的誤差、電壓互感器的合成誤差、電流互感器的合成誤差和電壓互感器二次導線壓降引起的計量誤差所組成,可以用以下式子表示:
ε=εw+εTA+εTV+εr
式中 εw—電能表誤差%
εTA—電流互感器合成誤差%
εTV—電壓互感器合成誤差%
εr—電壓互感器二次導線壓降引起的計量誤差%
在(zai)電(dian)(dian)廠及(ji)變電(dian)(dian)站(zhan)電(dian)(dian)能(neng)計量回(hui)路(lu)中,室(shi)外的(de)(de)電(dian)(dian)壓(ya)(ya)互(hu)感(gan)(gan)器離(li)裝設于控制室(shi)配(pei)電(dian)(dian)盤上的(de)(de)電(dian)(dian)能(neng)表(biao)有較(jiao)遠的(de)(de)距(ju)離(li),一般在(zai)200~400 m左(zuo)右(you),整個回(hui)路(lu)有接線(xian)端(duan)子排(pai)、開(kai)關、熔(rong)斷器及(ji)導線(xian),必然存在(zai)著(zhu)接觸電(dian)(dian)阻、導線(xian)電(dian)(dian)阻及(ji)分布參數(shu),從(cong)而就存在(zai)著(zhu)一定的(de)(de)回(hui)路(lu)阻抗,造成電(dian)(dian)壓(ya)(ya)互(hu)感(gan)(gan)器與電(dian)(dian)能(neng)表(biao)間(jian)的(de)(de)二(er)(er)(er)次回(hui)路(lu)上有電(dian)(dian)壓(ya)(ya)降。電(dian)(dian)壓(ya)(ya)互(hu)感(gan)(gan)器二(er)(er)(er)次回(hui)路(lu)壓(ya)(ya)降包括電(dian)(dian)纜、端(duan)子接觸電(dian)(dian)阻、熔(rong)線(xian)、中間(jian)繼電(dian)(dian)器接點、空氣小(xiao)開(kai)關等電(dian)(dian)壓(ya)(ya)降之總(zong)和。電(dian)(dian)壓(ya)(ya)互(hu)感(gan)(gan)器二(er)(er)(er)次電(dian)(dian)壓(ya)(ya)降引起的(de)(de)誤差,就是(shi)指電(dian)(dian)壓(ya)(ya)互(hu)感(gan)(gan)器二(er)(er)(er)次端(duan)子和負載端(duan)子之間(jian)電(dian)(dian)壓(ya)(ya)的(de)(de)幅值(zhi)差相對于二(er)(er)(er)次實際電(dian)(dian)壓(ya)(ya)的(de)(de)百分數(shu),以及(ji)兩(liang)個電(dian)(dian)壓(ya)(ya)之間(jian)的(de)(de)相位差的(de)(de)總(zong)稱。
主要技術指標
環境條件
——溫度:-5?C~40?C
——相對濕度:<95%(25?C)
——海拔高度:<2500m
——外界干擾:無(wu)特強震(zhen)動、無(wu)特強電磁場
PT電流互感器二次回路負載測試儀主要技術指標
1). PT二次負荷測試
——導納測量范圍:0.1ms—50.0ms
——導納測量準確度:
——二次電壓(50V-120V)
?X=?(2%×X+2%×Y)?2個字
?Y=?(2%×X+2%×Y)?2個字
2個字——儀器的量化誤差
注意:測量值在0.2mS以下時,測試電壓應保持在50V以上,同時注意鉗表的穿心導線保持居中。此時儀器量化誤差為5個字
2). 電(dian)壓(ya)表頭:0.5%
CT電流互感器二次回路負載測試儀主要技術指標
——阻抗測量范圍:0.1Ω—50.0Ω
——阻抗測量準確度:
?X=?(2%×X+2%×Y)?2個字
?Y=?(2%×X+2%×Y)?2個字
2個字——儀器的量化誤差
電流表頭:1%